INSPECTION REPORT
Health Protection
ZDER-CFFMV2
PREMISES NAME
Augusta Springs Swimming Pool
Tel: (604) 432-7774
Fax:
PREMISES ADDRESS
1695 Augusta Ave
Burnaby, BC V5A 4P1
INSPECTION DATE
June 15, 2022
TIME SPENT
1 hour
OPERATOR (Person in Charge)
NEXT INSPECTION DATE
2 Months
INSPECTION TYPE
Routine
ACTION TAKENPOOL SAFETY
ADMINISTRATIVE
Information Provided
ENFORCEMENT
Require Corrections


Comply

In Use

Pool Safety Plan

Yes

Yes

Operator Training

Yes

HAZARD RATING FOR YOUR FACILITY: Moderate (16-29) Total Score = 15
Critical Hazards: Total Number: 1
301 - Hot water provided in sanitary facilities not maintained at less than 49ÂșC [s.11(2)(g)]
Observation (CORRECTED DURING INSPECTION): Showers and sinks in cabana are noted between 59-61 C.
Corrective Action(s): Ensure all sanitary facilities are maintained under 49 C to prevent scolding/burns. Hot water tank adjusted during inspection.
Violation Score: 12

Non-Critical Hazards: Total Number: 1
410 - Pool chemicals / parameters not tested in accordance to Pool Regulation [s. 10(2)]
Observation: Alkalinity (Alk) and Stabilizer (STAB) not being tested for weekly.
Corrective Action(s): Ensure alkalinity and stabilizer is tested weekly. Currently water samples are taken to Imperial Paddock Pool company for testing where results and instructions of chemical adjustments are provided. This sampling happens every 10-14 days. Operator will look to adjust this to weekly so that Alk and STAB can be tested weekly and can bring the pool operation and testing into compliance.
Ensure to compare and add all testing results from pool company to main testing log book.
Correction date: immediately
Violation Score: 3

Comments

Routine:
FAC: 1.4 ppm (ideal 3-5ppm)
CAC: 0 ppm
pH: 7.6 (ideal 7.2-7.8)
CYA: 30 ppm (ideal 30-50 ppm, max 80 ppm for outdoor pools)
Alk: 80 ppm (ideal 80-120 ppm)
Temp: 24 C
Facilities: 61 C (Must be <49 C) (***violation noted above)
- Salt system (primary chlorination system) operational
-Safety equipment available
-Handrails secure
-Pool chemistry tested twice daily for FAC,CAC & pH
*No weekly testing being done for Alkalinity (Alk) or Cyanuric Acid (Stabilizer or CYA) (***violation noted above)
*Imperial paddock pool water sample tested every 10 days
-Deck markings clear
-Skimmers & weirs operational
-Equalizer lines plugged
-Deck maintained in good condition
-Facility sanitation satisfactory
-PSP up to date
-Operating Permit posted

***Pool approved to open for Summer 2022 Season