Inspection Information:
Facility Type: | WS4 |
Inspection type: | Routine |
Inspection date: | October 09, 2019 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
318 | Inadequate Microbiological Analysis data Observation: Water samples are not being submitted on a monthly basis as outlined in the permit. monthly samples allow to notice any changes in the water quality, or a breakdown in the treatment processes. Corrective Action: Increase samples to at least once a month. Sampling responsibilities can be delegated to others provided they are trained on the proper sampling protocols. |
319 | Inadequate Chemical Analysis Data Observation: Manganese concentration from a sample taken in 2016 indicated the concentration was 0.248 ppm which is above the new MAC issued by Health Canada of 0.12 ppm. Corrective Action: Have an accredited laboratory determine the current concentration of manganese and if it is still over the limit, then treatment will need to be enhanced to remove the manganese from the drinking water. |