Nukko Lake Hall - Inspection Report

Inspection Information:
Facility Type:  WS4
Inspection type:  Routine
Inspection date:  October 09, 2019
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
318   Inadequate Microbiological Analysis data
Observation: Water samples are not being submitted on a monthly basis as outlined in the permit. monthly samples allow to notice any changes in the water quality, or a breakdown in the treatment processes.
Corrective Action: Increase samples to at least once a month. Sampling responsibilities can be delegated to others provided they are trained on the proper sampling protocols.
319   Inadequate Chemical Analysis Data
Observation: Manganese concentration from a sample taken in 2016 indicated the concentration was 0.248 ppm which is above the new MAC issued by Health Canada of 0.12 ppm.