SURF WATER SYSTEM - Inspection Report
This facility was given high hazard rating. More info
Inspection Information
Facility Type2-14 (DWS)
Inspection typeRoutine
Inspection dateSeptember 09, 2021
Follow-up RequiredNo
Violations: A summary of the violations found during the inspection are listed below.
Code Description / Observation / Corrective Action
313  Critical Other (specify below)
Corrective Action: 1) Water samples are to be submitted BIWEEKLY (twice a month) for bacteriological analysis as per conditions on your Operating Permit Appendix A. In 2021, samples were NOT submitted AT ALL for the months of April, May, July, and August. This is unacceptable and must be rectified IMMEDIATELY or further actions such as the issuance of a violation ticker, issuance of an Order, etc. may occur. Obtain the services of water maintenance/sampling company as discussed. 2) Chlorine residual levels are to be documents and measured at least three (3) times per week in your log book and kept onsite as per Appendix A conditions on your Operating Permit. Again, this is to be corrected immediately or further actions may be taken as mentioned above. Log book to be kept in pumphouse so that maintenace logs can be viewed by maintenance company. 3) Continue with disinfection by-product monitoring as per several emails to you (latest email dated July 16, 2021 and August 3, 2021). As the disinfection by-product analysis was not conclusive in July 16, 2021, repeat analysis on the treated distribution water immediately and forward results to this office by September 24, 2021. Repeat disinfection by-product analysis November 2021 and February 2022 with results forwarded to our office.